Marine Equipment

LDZBJ10-12G Current Transformer

LDZBJ10-12G  Current Transformer Working conditions Ambient temperature: -25C --+40C, the daily average does not exceed 30C The altitude does not exceed 2500m 1. Ratings and pe...

Marine Transformers1 Photos ISO9001 Supplier

LDZBJ10-12G Current Transformer

Certificate: ABS, LR, BV, DNVGL, NK, KR, IRS, RMRS, CCS
Warranty: 12 Months unless specified otherwise
Place of Origin: China

We can supply according to your requirement.

LDZBJ10-12G Current Transformer

Working conditions Ambient temperature:
-25C --+40C, the daily average does not exceed 30C
The altitude does not exceed 2500m
1. Ratings and performance requirements
1.1 The rated voltage is 12 kV.
1.2 Rated frequency 50-60HZ.
1.3 Rated primary current: 200:400:600A.
1.4 Rated secondary current: 5A.
1.5 Rated secondary load: 15VA COSφ=0.8.
1.6 Accuracy: 10P
1.7 Accuracy class limit coefficient: 10.
1.8 Short-time current rating
1.9 Rated short-time thermal current
The secondary coil of the transformer is short-circuited, and the primary coil should be able to withstand a thermal current of 30KA for 1 second
2.0 rated dynamic stable current
The secondary coil of the transformer is short-circuited The primary coil should be able to withstand the rated dynamic stable current
2.1 Temperature rise
The insulation class of the transformer is E-class, and the temperature rise of the primary and secondary windings should not exceed 75K during long-term operation under the rated secondary load and rated primary current.

Send us your inquiry now

We will respond within 24 hours with the sales or technical contact.

Verification code image

Quality Assurance

Safe and reliable products for marine & offshore projects.

Professional Service

One-stop service from inquiry to delivery.

Fast Delivery

Stable logistics ensure safe on-time arrival.

Inquiry